EG-37 Low Voltage Short Circuit and Grounding

Eg-37 Low Voltage Short Circuit And Grounding

DEFINITION

EG-37 AG Short Circuit and Grounding equipment is a system that ensures the life safety of employees by short-circuiting the line and grounding it while working in energy carrying lines and centers.

STUDY

EG-37 AG Short Circuit and Grounding equipment clips are attached to each phase of the line, lighting line, neutral line, and the system is short-circuited by joining the branch cables of the clips together with the down cable. The entire system is grounded by connecting the landing cable to the grounding stake or grounding line. This protection is made from both sides of the studied area. The clips are used with a screwing system to grasp the 3mm to 20mm ø round and 3mm to 20mm thick flat bar or lines.

CAUTION!..

General safety rules to be taken when using LV SHORT CIRCUIT AND GROUNDING Equipment:

1. Cut off the voltage from the main switch of the part of the system to be worked on.

2. If there is a safety lock on the panel, install the lock according to the absence of voltage.

3. Check with LV detector that there is no voltage in the conductors and devices and make sure that there is no voltage.

4. Connect the grounding and short-circuit equipment to the system, starting with the grounding stake and clamp. Disconnect the last grounding when disassembling.

5. Mark the work area with a barrier or sign. Operating Voltage : Max. 0.72kV